| Plan Review Notes For Permit 01101847 |
| Permit Number |
01101847 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-01 00:00:00 | 1) NO SMOKE DETECTOR LOCATED ABOVE FIRE | | | ALARM CONTROL PANEL. | | | 2) MANUAL PULL-STATIONS NOT PRESENT | | | AT ALL EXIT DOOR LOCATIONS. | | | 3) NO CUT-SHEETS PROVIDED FOR FIRE | | | ALARM EQUIPMENT PLANNED FOR USE. | | | 4) PLEASE INDICATE ON PLANS, MOUNTING | | | HEIGHTS FOR FIRE ALARM EQUIPMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|