| Plan Review Notes For Permit 01101823 |
| Permit Number |
01101823 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101823 | | | 100 FLAGLER LN. | | | CONT JAMES L RICE | | | TEL (561) 495-8640 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS STANDARD BUILDING CODE | | | | | | 1)- LOT IS LOCATED IN AA-5 FLOOD ZONE. | | | WILL REQUIRE A SURVEY INDICATING THE | | | ELEVATION OF THE FINISH FLOOR OF THE | | | RESIDENCE & GARAGE. | | | | | | 2)- SOILS REPORT SBC 1804.2.7.2 (7)* | | | MINIMUM SAFE BEARING VALUE. | | | | | | 3)-FL ENERGY SHEETS DO NOT REFLECT A | | | FIRE PLACE, ALSO THAT THERE IS NO DOORS | | | ON FIREPLACE. | | | | | | 4)- OWNER, AGENT OR CONTRACTOR TO SIGN | | | ENERGY SHEETS. | | | | | | 5MISSING PRODUCT APPROVAL REPORTS FOR: | | | GLAZED OPENINGS, | | | WINDOWS, FIXED AND OPERITABLE | | | DOORS SWING | | | DOORS SLIDING | | | GARAGE DOOR REUSE. | | | ROOFING MATERIALS: SHINGLES | | | | | | SBC 2606.1 FACTORY BUILT FIREPLACES | | | MANUFACTURES SPEC CONFORMING TO UL 127 | | | SBC2810 FRESH AIR INTAKE | | | SBC 2804.4 FACTORY BUILT CHIMNEYS: MEET | | | THE REQUIREMENTS OF UL 127 | | | | | | SBC 1203.4.2. BATHROOMS 107/ 204 NEED TO | | | MEET THE REQUIREMENT OF MECHANICAL VENTI | | | LATION FOR THESE ROOMS. | | | | | | PLANS ARE TO BE REVIEWED BY COUNTY | | | FOR COUNTY IMPACT FEES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|