| 2001-12-22 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) PROVIDE EMERGENCY EGRESS WINDOW IN | | | THEATER ROOM WHICH COULD BE USED AS A | | | SLEEPING ROOM. 97 SBC 1005.4 | | | | | | 2) THE ENERGY CALCULATION FORMS ARE | | | REQUIRED TO BE SIGNED AND DATED BY THE | | | OWNER/AGENT. | | | | | | 3) THE EXTERIOR WALL WITHIN 3 FEET OF | | | THE PROPERTY LINE IS REQUIRED TO HAVE A | | | 1 HOUR FIRE RESISTANCE RATING PER TABLE | | | 600 OF THE 97 SBC. EXTERIOR WALLS WITHIN | | | 5 FEET OF ASSUMED PROPERTY LINE MUST BE | | | DESIGNED FOR FIRE RESISTANCE BY ASSUMING | | | EITHER SIDE OF THE WALL TO BE EXPOSED TO | | | FIRE. 97 SBC 709.6 | | | | | | 4) PROVIDE A KEY PLAN, INSTALLATION | | | SCHEDULE AND INDICATE TYPE OF FASTENERS | | | TO BE USED FOR STORM PANELS. INDICATE | | | THAT ADEQUATE SUBSTRATE (BACKING) WILL | | | BE PROVIDED AT OPENINGS FOR ATTACHING | | | STORM PANELS. | | | | | | 5) REVISED PLANS WITH CHANGES TO | | | EXTERIOR WILL REQUIRE REVIEW BY THE | | | HISTORIC PRESERVATION DIVISION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|