Plan Review Notes
Plan Review Notes For Permit 01101790
Permit Number 01101790
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-02 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING IN
 FORMATION FOR REVIEW.
  
 1.MANUFACTURER, MODEL, BTU AND SEER
 OF NEW A/C EQUIPMENT BEING INSTALLED
  
 2.INDICATE LOCATION OF AHU.
  
 3.INDICATE SIZE AND OF CONDENSATE,
 LIQUID AND SUCTION LINES.
  
 4.TERMINATION OF CONDENSATE.
  
 5.INDICATE SIZE, MATERIAL AND R-VALUE
 OF DUCTWORK.
  
 6.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS AS PER FLORIDA ENERGY
 CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.