| Plan Review Notes For Permit 01101674 |
| Permit Number |
01101674 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-28 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NOTE, THE LOAD CALCULATIONS | | | THAT WERE SUBMITTED DO NOT MEET NEC. | | | PLEASE NOTE THAT THE ORIG LOAD SUBMITTED | | | WAS ALMOST 200AMPS AND NOW THE NEW | | | LOAD CALCS SUBMITTED ARE MISSING MANY | | | LOADS THAT ARE REQ`D FOR MIN NEC LOAD | | | REQUIREMENTS. | | | | | | PLEASE SUBMIT FOR REVIEW OR HAVE | | | ELECTRICAL PERMIT UNDER THIS PRIME | | | VOIDED SO THE POOL PERMIT MAY BE ISSUED | | | AND ELECTRICAL CONTRACTOR CAN SUBMIT | | | ELECTRICAL PLANS AND PERMIT APPLICATION | | | SEPARATELY. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|