 THIS REVIEW WAS DONE WITH CAPT MIKE
 CARSILLO, NANCY DEMARK, JIM WHITMERE &
 PATTY KRAUSS
  
 VENT LINE TO TANK - SHALL COMPLY WITH
 1997 SMC 1105.7.2.
  
 PLEASE PROVIDE MSDS SHEETS ON THE
 AMMONIA TYPE SPECIFIC TO THIS
 APPLICATION.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA FOR
 THE DOUBLE WALL FIBERGLASS TANK.AS PER
 ASHRAE 15-1992 10.4.8.2, TANK SHALL BE
 SUBSTANTIALLY CONSTRUCTED OF NOT LESS
 THAN 1/8 IN OR NO. 11 U.S. GAGE IRON OR
 STEEL.
  
 INDICATE WHO MAKES THE DETERMINATION
 WHEN THE SYSTEM IS TO BE DUMPED INTO
 THE TANK.WILL THIS BE A MANUAL OR
 MONITORED SYSTEM.
  
 PROVIDE PLAN FOR ACTION IF LEAK OCCURS
 WHEN BUILDING IS NOT OCCUPIED TO PROVIDE
 NOTIFICATION.AS PER ASHRAE 15-1999
 B10,THE RELEASE OF AMMONIA INTO THE
 ATMOSHERE IN THE EVENT OF AN EMERGENCY,
 MAY BE SUBJECT TO THE REPORTING REQUIREM
 ENTS OF THE 'EMERGENCY PLANNING & COMMUN
 ITY RIGHT-TO-KNOW ACT OF 1986.IN LOCAT
 IONS WHERE ATMOSHPERIC RELEASE MAY BE
 HAZARDOUS DUE TO THE PROXIMITY OF PEOPLE
 OR OTHER PREMISES.
  