| 2002-01-04 00:00:00 | |
| | THIS REVIEW WAS DONE WITH CAPT MIKE |
| | CARSILLO, NANCY DEMARK, JIM WHITMERE & |
| | PATTY KRAUSS |
| | |
| | VENT LINE TO TANK - SHALL COMPLY WITH |
| | 1997 SMC 1105.7.2. |
| | |
| | PLEASE PROVIDE MSDS SHEETS ON THE |
| | AMMONIA TYPE SPECIFIC TO THIS |
| | APPLICATION. |
| | |
| | PROVIDE MANUFACTURER SUBMITTAL DATA FOR |
| | THE DOUBLE WALL FIBERGLASS TANK.AS PER |
| | ASHRAE 15-1992 10.4.8.2, TANK SHALL BE |
| | SUBSTANTIALLY CONSTRUCTED OF NOT LESS |
| | THAN 1/8 IN OR NO. 11 U.S. GAGE IRON OR |
| | STEEL. |
| | |
| | INDICATE WHO MAKES THE DETERMINATION |
| | WHEN THE SYSTEM IS TO BE DUMPED INTO |
| | THE TANK.WILL THIS BE A MANUAL OR |
| | MONITORED SYSTEM. |
| | |
| | PROVIDE PLAN FOR ACTION IF LEAK OCCURS |
| | WHEN BUILDING IS NOT OCCUPIED TO PROVIDE |
| | NOTIFICATION.AS PER ASHRAE 15-1999 |
| | B10,THE RELEASE OF AMMONIA INTO THE |
| | ATMOSHERE IN THE EVENT OF AN EMERGENCY, |
| | MAY BE SUBJECT TO THE REPORTING REQUIREM |
| | ENTS OF THE 'EMERGENCY PLANNING & COMMUN |
| | ITY RIGHT-TO-KNOW ACT OF 1986.IN LOCAT |
| | IONS WHERE ATMOSHPERIC RELEASE MAY BE |
| | HAZARDOUS DUE TO THE PROXIMITY OF PEOPLE |
| | OR OTHER PREMISES. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |