| Plan Review Notes For Permit 01101647 |
| Permit Number |
01101647 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101647 | | | 5881 45TH STREET | | | | | | 1)- THE PLAN FOR "DUMPING" OF THE | | | ANHYDROUS AMMONIA INTO THE 25,000 GAL | | | UNDERGROUND TANK WILL REQUIRE ADDITIONAL | | | INFORMATION. | | | 2) WE WILL NEED TO KNOW THE VOLUME OF | | | AMMONIA THAT WILL BE IN THE SEALED | | | SYSTEM. THE CALCULATIONS INDICATING HOW | | | MUCH WATER SHALL BE REQUIRED TO NEUTRAL- | | | IZE THE AMMONIA. | | | 3) MSDS SHEETS FOR THE R-717 OR | | | ANHYDROUS AMMONIA. | | | 4) THE PROCEDURE INVOLVED IF A ACCIDENT | | | DOES OCCUR?? | | | 5) SAFETY DEVISES SENSORS? | | | 6) SARA SECTION 302/304 EMERGENCY PLAN- | | | NING AND NOTIFICATION, | | | REPORTABLE QUANTITY 100 LBS | | | THRESHOLD PLANNING500 LBS. | | | | | | THIS REVIEW IS NOT TO BE CONSIDERED | | | A THROUGH REVIEW UNTIL THE ABOVE COM- | | | MENTS HAVE BEEN ADDRESSED, MORE COMMENTS | | | MAY BE FORTH COMING WITH THE NEW INFORMA | | | TION. THIS APPLICATION FOR PERMIT MAY BE | | | ONLY FOR THE TANK BUT THE CONCERNS ARE | | | THAT IF IN CASE OF A LEAK WE DO HAVE THE | | | PROPER SAFETY PROCEDURES IN AFFECT. |
|