| Plan Review Notes For Permit 01101634 |
| Permit Number |
01101634 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-07 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT EVEN RECESSED | | | FIXTURE IN CLOSET IS SHOWN TOO CLOSE. | | | PER 410-8 MAY BE FLOURESCENT ON WALL, | | | ABOVE DOOR. | | | | | | 2)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS SUBMITTED WERE ONLY FOR | | | DETACHED BLDG. PLEASE INLCUDE MAIN | | | HOUSE. | | | | | | 3)NOTE: PLEASE NOTE THAT A RISER | | | DIAGRAM WAS STILL NOT SUBMITTED FOR | | | REVIEW FOR FEED FROM EXSITING SERVICE. | | | | | | 4)NOTE: PLEASE NOTE GROUNDING DETAIL | | | FOR DETACHED BLDG NOT SHOWN PER 250-32 | | | | | | | | | PLEASE PICK UP PLANS AND RESUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|