Plan Review Notes
Plan Review Notes For Permit 01101634
Permit Number 01101634
Review Stop E
Sequence Number 2
Notes
Date Text
2002-02-07 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT EVEN RECESSED
 FIXTURE IN CLOSET IS SHOWN TOO CLOSE.
 PER 410-8 MAY BE FLOURESCENT ON WALL,
 ABOVE DOOR.
  
 2)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS SUBMITTED WERE ONLY FOR
 DETACHED BLDG. PLEASE INLCUDE MAIN
 HOUSE.
  
 3)NOTE: PLEASE NOTE THAT A RISER
 DIAGRAM WAS STILL NOT SUBMITTED FOR
 REVIEW FOR FEED FROM EXSITING SERVICE.
  
 4)NOTE: PLEASE NOTE GROUNDING DETAIL
 FOR DETACHED BLDG NOT SHOWN PER 250-32
  
  
 PLEASE PICK UP PLANS AND RESUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372