Plan Review Notes
Plan Review Notes For Permit 01101634
Permit Number 01101634
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-29 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT OUTLETS SHOWN
 FOR BATHS NEED TO BE SHOWN AS GFI/
 ALSO MUST BE 20A AND #12 210-8,210-11-C
 -3.
  
 2)NOTE: PLEASE NOTE THAT SD`S WILL BE
 REQ`D INSIDE AND OUTSIDE BEDROOMS.
 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE NOTE THAT LIGHT IN CLOSET
 NEEDS TO MEET 410-8 FOR CLEARENCE AND
 TYPE OF FIXTURE.
  
 4)NOTE: PLEASE NOTE WATER HEATER IS
 NOT PERMITTED IN CLOSET WITH IGNITABLE
 MATERIALS. A SEPARATE WALL WOULD HAVE TO
 BE BUILT FOR CLEARENCE/SEPARATION.
 422-17
  
 5)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW ENOUGH INFORMATION FOR PANEL AND
 HOW OR WHERE IT IS BEING FED?? WIRE/
 CONDUIT? GROUNDING? LOAD CALCULATIONS?
 EXSITING ? NEW? 215-5
  
 6)NOTE: PLEASEOUTLET OUTSIDE NEEDS TO
 BE SHOWN AS GFI 210-8
  
 **PLEASE NOTE THAT PLAN WILL NEED TO
 BE REVIEWED BY ZONING FOR ACCESSORY
 SLEEPING UNIT.*****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372