| Plan Review Notes For Permit 01101632 |
| Permit Number |
01101632 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-25 00:00:00 | | | | PIPE SHALL BE TESTED TO 1 1/2 TIMES | | | WORKING PRESSURE OR NOT LESS THAN 100 | | | PSI WIHICHEVER IS GREATER.TEST IS | | | ONLY REQUIRED FROM SHUTOFF VALVESNOT | | | FOR THE ENTIRE SYSTEM. | | | | | | NOTE, CONDENSER WATER PIPING SHALL BE | | | BRAZED AS PER 1997 SMC TABLE 1205. |
|