2001-11-08 00:00:00PROVISO:
 DUCT SMOKE DETECTOR TO BE TIED TO BLDG
 FIRE ALARM SYTEM FOR NOTIFICATION PER
 NFPA 90A 4-4.4.3
 IF NO BLDG FIRE ALARM SYSTEM PROVIDE
 HORN AND STROBE FOR NOTIFICATION NFPA
 90A 4-4.4.4