| 2001-11-08 00:00:00 | PROVISO: | | | DUCT SMOKE DETECTOR TO BE TIED TO BLDG | | | FIRE ALARM SYTEM FOR NOTIFICATION PER | | | NFPA 90A 4-4.4.3 | | | IF NO BLDG FIRE ALARM SYSTEM PROVIDE | | | HORN AND STROBE FOR NOTIFICATION NFPA | | | 90A 4-4.4.4 |
|