2001-11-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101603
 222 LAKEVIEW SUITE 164/166/168
 CONT KOLTER SIGNATURE HOMES, INC
 TEL: (561) 468-4703
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- CITY CODE 7.2 ALLOWS FOR THE BUILD-
 ING DEPARTMENT TO CALCULATE THE PERMIT
 FEES USING THE FEE TABLE SET UP THROUGH
 SBCCI WITH A FLORIDA MULTIPLIER. YOUR
 PERMIT VALUE IS NOT REALISTIC, TOO LOW,
 EITHER PRODUCE A SIGNED CONTRACT OR THE
 VALUES WILL BE TAKEN FOR TYPE II CON-
 STRUCTION, FLORIDA MULTIPLIER AND
 REDUCED 50% SINCE THE STRUCTURE IS NOT
 TO BE CONSIDERED.CALCULATED FIGURE WITH
 50% REDUCTION IS:
 (1814SQ FT X $106.08) X 50%=$96,214.56.
  
 2)- SBC 1001.1.3 ALLOWS FOR THE USE OF
 OFFICE TO BE USED AS A SECOND MEANS OF
 EGRESS, SEC 1020 ALLOWS FOR SINGLE MEANS
 OF EGRESS IF:
 A) A MAXIMUM OF 2 STORIES IN HEIGTH
 B) EACH FLOOR AREA SERVED DOESN'T
 EXCEED 3,500 SQ FT
 C) NO MORE THAN 40 PEOPLE ABOVE THE
 STREET FLOOR
 D) THE MAXIMUM TRAVEL DISTANCE TO A
 SINGLE EXIT DOES NOT EXCEED 75'.
 THIS OFFICE MEETS REQUIREMENTS FOR
 SINGLE MEANS OF EGRESS THROUGH THE
 BUILDING CODE.
  
 3) THIS IS A TYPE II BUILDING,
 SBC 609.2.1 NO COMBUSTIBLE MATERIALS IN
 WALLS. FIRE RESISTANT TREATED WOOD MAY
 BE USED AS SILL, OR BACKING MATERIAL.
  
 4) MISSING THE MINIMUM INTERIOR FINISH
 CLASSIFICATION SBC TABLE 803.3.
  
 5) TYPE 1 & II BUILDINGS REQUIRE FIRE
 SPRINKLER PLANS AS PART OF THE BUILDING
 PERMIT PACKAGE. SEPERATE PLANS, FEES &
 PERMIT REQUIRED FOR FIRE SPRINKLERS.
  
 6)- FLOOR FINISHES NOT INDICATED:
 FL ACCESS CODE 4.5 FLOOR SURFACES ALONG
 ACCESIBLE ROUTES AND IN ACCESSIBLE ROOMS
 SPACES INCLUDING FLOORS ,RAMPS AND
 STAIRS SHALL BE STABLE, FIRM, AND
 SLIP RESISTANT. ADDAAG A-5 A STATIC
 COEFFICIENT OF FRICTION OF 0.6 FOR ALL
 ACCESSIBLE ROUTES & 0.8 FOR RAMPS.
  
 7)SEE KITHEN & RESTROOM NOTES:
 WATER CLOSET: FL ACCESS CODE 4.16.3
 THE HEIGTH OF THE WATER CLOSET SHALL BE
 17" TO 19" MEASURED TO THE TOP OF THE
 TOLIET SEAT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412