| Plan Review Notes For Permit 01101545 |
| Permit Number |
01101545 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-01 00:00:00 | PROVISO: | | | | | | ACCEPTANCE TEST OF STAIRWAY | | | PRESSURIZATION REQUIRED FOR FINAL. | | | CONTACT THE FIRE INSPECTOR AND MYSELF | | | FOR COORDINATION OF TIME/DATE FOR TEST. | | | INDEPENDANT TEST AND BALANCE COMPANY | | | WILL BE REQUIRED TO CONDUCT TEST | | | INCLUDING DOOR PULLS AND DIFFERENTIAL | | | PRESSURE ACROSS STAIR WAY DOORS IN | | | ACCORDANCE WITH NFPA 92A AND | | | CONSTRUTION SERVICES MECHANICAL | | | REQUIREMENTS. | | | PRETEST OF SYSTEM EXPECTED PRIOR TO | | | SCHEDULING TEST WITH CITY INSPECTORS | | | | | | ANY QUESTIONS ON TEST CRITERIA CONTACT | | | NANCY DENMARK, CHIEF MECHANICAL | | | INSPECTOR @ (561) 659-8096 EXT. 8221 |
|