| Plan Review Notes For Permit 01101544 |
| Permit Number |
01101544 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-05 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CHANGES | | | THAT ARE HAND DRAWN ON PLANS MUST BE | | | SIGNED AND DATED BY THE ARCH OF RECORD | | | PER 481.221. OF THE FS/FAC. | | | | | | 2)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | | MENTIONS ONE NEW A/C SYSTEM AND PLANS | | | SHOW TWO NEW A/C SYSTEMS? PLEASE CLARIFY | | | | | | | | | 3)NOTE: PLEASE CLARIFY EXSITING LOAD AND | | | SIZE OF EXISTING SERVICE. | | | | | | 4)NOTE: PLEASE NOTE THAT APPEARS THAT | | | SMOKE DETECTORS ARE BEING INSTALLED TO | | | MEET CODE. PLEASE NOTE ONLY MISSING ONE | | | ON LOWER LEVEL. NFPA-72 2-2.1.1.1 | | | | | | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 6)NOTE: PLEASE NOTE MISSING ONE OUTLET | | | SERVING KITCHEN COUNTERSPACE TO BE SHOWN | | | AS GFI. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|