| Plan Review Notes For Permit 01101533 |
| Permit Number |
01101533 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FLOOR DRAIN NOT SHOWN IN BATHROOM. | | | PER SPC SEC 409.4.1.1 A FLOOR DRAIN IS | | | REQUIRED WITH A TRAP PRIMER. SHT A-1 | | | 2) SHT M-1, PLEASE ADD DRINKING FOUNTAIN | | | TO RISER DIAGRAM. SHOW TIE IN AND VENT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|