| Plan Review Notes For Permit 01101533 |
| Permit Number |
01101533 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-03 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) TOILET ROOM TO COMPLY WITH FACBC - | | | SEC 4.22. PLEASE SUBMIT DETAILS SHOWING | | | COMPLIANCE FOR ALL DETAILS OF THIS SECT- | | | ION OF FACBC-97. W/C 4.16 - LAV 4.19 - | | | CLEAR FLOOR SPACE - TURNING RADIUSECT. | | | 2) PAGE A-1 TOILET ROOM REQUIRED TO HAVE | | | A FLOOR DRAIN WITH A TRAP PRIMER PER SPC | | | SEC 409.4.1.1. | | | 3) PAGE A-1 DRINKING FOUNTAIN REQUIRED | | | PER SPC TABLE 407. SUBMIT DETAILS FOR | | | DRINKING SHOWING COMPLIANCE WITH FACBC | | | SEC 4.15 AND SEC 4.1.3(10) PROVISIONS | | | FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING IF A HI/LOW DRINKING FOUNTAIN | | | IS NOT INSTALLED. | | | 4) PAGE A-1 PLEASE CLAIRFY WATER DETAIL | | | AT WAITING ROOM | | | 5) PAGE A-1 DEVELOPER RM. PLEASE INDIC- | | | ATE WHAT CHEMICALS IF ANY ARE USED FOR | | | DEVELOPEMENT. SHOW IF CHEMICALS ARE BIO- | | | DEGRADEABLE OR NOT. | | | 6) PAGE M-1 PLUMBING RISER NOT APPROVED. | | | SINK NOT VENTED. | | | 7) RPZ BACKFLOW REQUIRED ON WATER | | | SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|