| Plan Review Notes For Permit 01101533 |
| Permit Number |
01101533 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-30 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS SHOW A | | | NEW 100A SUB PANEL, BUT EXISTING MAIN | | | PANEL DOES NOT LIST ON SCHEDULE?? | | | | | | 2)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED???215-5 | | | CONTINUOUS LOADS AT 125%. | | | | | | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN EXIST AND | | | NEW PANEL.250-122 | | | | | | 4)NOTE: PLANS NEED TO SHOW ALL BRANCH | | | CIRCUITING AND CORRELATE WITH SUBMITTED | | | PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW EQUIPMENT. 110-9 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|