Text |
| 2002-05-22 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-SOIL TEST REPORT CALLS FOR FOUNDATION |
| | TO BE 16" MINIMUM WIDTH. FOUNDATION |
| | PLAN CALLS FOR 12"W. REVISE/CLARIFY AS |
| | REQUIRED. |
| | 3-CONCRETE SLAB: PROVIDE JOINT DESIGN |
| | AND SPECS AS REQUIRED BY SEC. 1909.3 |
| | FBC 2001. (IF APPLYING EXCEPTION, THEN |
| | SPECIFY SUPPORTS). |
| | 4-SPECIFY ON PLANS THAT GLASS BLOCK TO |
| | BE 1 HR FIRE RATED AT ZERO LOT LINE |
| | WALL AS REQUIRED BY TABLE 600 FBC 2001 |
| | PROVIDE UL LISTING AND SPECS FOR 1HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | 5-CLARIFY SIZE OF EGRESS WINDOW AT BEDRM |
| | #3. FLOOR PLAN CALLS FOR ONE SIZE AND |
| | EXTERIOR ELEVATION FOR ANOTHER. MAKE |
| | SURE THAT SELECTED ONE MEETS THE MIN. |
| | CLEAR HEIGHT OPENING (24") REQUIRED BY |
| | SECTION 1005.4.4 FBC 2001. |
| | 6-TRUSS DRAWINGS: |
| | A)CLARIFY GABLE END TRUSSES DESIGN. |
| | NOTES SAY THAT TRUSS TO BE BRACED |
| | ACCORDING TO THE STANDARD GABLE END |
| | DETAIL, BUT ON THE OTHER HAND OTHER |
| | NOTEON THE SAME PAGE SAYS THAT TRUSS |
| | WAS DESIGNED FOR A NON-GABLE ZONE. |
| | REVISE/CLARIFY SUCH CONFLICT. |
| | B)UPDATE ALL GENERAL TRUSS DETAILS TO |
| | MATCH THE NEW CODE USED ASCE 7-98 FOR |
| | 140MPH. |