| 2001-11-29 00:00:00 | CHECKLIST: |
| | 1-REAR ELEVATION EXCEEDS THE MAXIMUM |
| | AMOUNT OF OPENING PERCENTAGE ALLOWED |
| | BY TABLE 600 OF SBC 1997. REVISE AS |
| | REQUIRED. |
| | 2-REVISE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA: SEE SEC. 604.1.A.1 |
| | OF FLORIDA ENERGY CODE, 1997 ED. |
| | -WALLS: THERE IS NOT EXT. FRAME WALL. |
| | -REVISE # OF BEDROOMS: SEE BEDROOM |
| | DEFINITION ON FL. ENERGY CODE, 1997 ED |
| | 3-PROVIDE CURRENT UL ASSEMBLY # FOR ONE |
| | HR FIRE RATED GLASS BLOCK ASSEMBLY. |
| | 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| | ENTRY DOORS. |
| | 5-TRUSS DRAWINGS: |
| | -UPDATE GENERAL DETAILS. USE ASCE 7-95 |
| | FOR 140MPH, NOT ASCE 7-93 110MPH OR |
| | USE SBC 1997 FOR 110 MPH. |
| | -MAKE SURE ALL DETAILS AND NOTES ARE |
| | LEGIBLE. |
| | -REVIEW STAMP ON TRUSS LAYOUT DOESN'T |
| | IDENTIFY THE FIRM WHO REVIEW ALL TRUSS |
| | DRAWINGS. (NOTE: ENGINEER SHALL NOT |
| | SIGN AND SEAL THESE DRAWINGS. ONLY THE |
| | STANDARD REVIEW STAMP IS REQUESTED). |
| | 6-SOIL TEST REPORT ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 OF FLORIDA STATUTES. |
| | 7-SEE PLANS FOR ADDITIONAL COMMENTS. |