| 2001-11-29 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE AO: WILL NEED THE ELEVATION |
| | CERTIFICATE. |
| | 2-REVISE ENERGY CALCULATIONS: |
| | -REVISE UNDER ATTIC AREA. SEE SECTION |
| | 604.1.A.1 FL. ENERGY CODE, 1997. |
| | 3-PROVIDE CURRENT UL ASSEMBLY FOR FIRE |
| | RATED GLASS BLOCK ASSEMBLY. |
| | 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| | ENTRY DOORS. |
| | 5-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| | AHU. SPECIFY ALL CONNECTORS. SECTION |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 6-REVISE WINDOW SIZE FOR BEDROOM #3: |
| | 24 SH WINDOW DOESN'T PROVIDE THE 24" |
| | MIN. CLEAR HEIGHT OPENING REQUIRED BY |
| | SEC. 1005.4 SBC 1997. |
| | 7-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 SBC 1997. |
| | 8-TRUSS DRAWINGS: |
| | -UPDATE GENERAL DETAILS. USE ASCE 7-95 |
| | FOR 140 MPH NOT, ASCE 7-93 FOR 110MPH. |
| | -SEE GENERAL DETAILS FOR COMMENTS. |
| | -MAKE SURE ALL DETAILS ARE LEGIBLE. |
| | -REVIEW STAMP DOESN'T IDENTIFY THE |
| | NAME OF FIRM WHO REVIEWED ALL TRUSS |
| | DRAWINGS. ENGINEER OF RECORD DOESN'T |
| | NEED TO SEAL THE TRUSS LAYOUT. JUST |
| | USE THE STANDARD REVIEW STAMP. |
| | 9-REVISE THE ROOF SHEATHING SPECS ON |
| | THE TYPICAL WALL SECTION. SEE SECTION |
| | 2306 OF CITY AMENDMENTS TO SBC 1997. |
| | 10-SOIL TEST REPORT ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 OF FLORIDA STATUTES. |