| Plan Review Notes For Permit 01101440 |
| Permit Number |
01101440 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | ************BUILDING PROVISO************ | | | | | | SBC 104.2.2 | | | | | | 1. A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2. THE ENERGY CODE INCORRECTLY LISTS | | | SOME EXTERIOR WOOD WALLS.PLEASE | | | CLARIFY. SUBMIT CORRECTED ENERGY FORMS. | | | | | | 3. SUBMIT CURRECT PRODUCT APPROVAL FOR | | | FRONT DOOR. SUBMITTED COPY EXPIRED. | | | | | | 4. SURVEY SHOWS LOT LOCATED IN AO FLOOD | | | ZONE.ELEVATION CERTIFICATE MUST BE | | | SUBMITTED BEFORE C/O CAN BE ISSUED. | | | | | | 5. SOIL REPORT STATES FOOTINGS TO BE | | | BETWEEN 16"-36" WIDTH.PG. 1 OF PLANS | | | SHOW FOOTINGS AS 12" WIDE. PLEASE | | | CLARIFY. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 659-8096 EXT. 8394 |
|