| Date |
Text |
| 2001-11-28 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE AO: NEED THE ELEVATION |
| | CERTIFICATE. |
| | 2-REVISE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA IS INCORRECT. SEE |
| | SECTION 604.1.A.1 OF FL. ENERGY CODE. |
| | -REVISE NUMBER OF BEDROOMS. SEE BEDRM |
| | DEFINITION ON FL. ENERGY CODE. |
| | 3-GLASS BLOCK INFORMATION IS TOO OLD. |
| | YEAR 1992. PROVIDE CURRENT UL FIRE |
| | RATED ASSEMBLY NUMBER. |
| | 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| | ENTRY DOORS. |
| | 5-TRUSS DRAWINGS: |
| | -UPDATE GENERAL DETAILS. USE SBC 1997 |
| | FOR 110MPH OR ASCE 7-95 FOR 140MPH. |
| | SEE COMMENTS ENGINEERED TRUSSES. |
| | -SOME DETAILS ARE NOT LEGIBLE. |
| | -REVIEW STAMP BY ENGINEER DOESN'T |
| | IDENTIFY THE FIRM WHO REVIEW THE TRUSS |
| | DRAWINGS. PROFESSIONAL ENGINEER OF |
| | RECORD DOESN'T HAVE TO SEAL THE TRUSS |
| | LAYOUT. HE ONLY NEEDS THE REVIEW STAMP, |
| | BUT IDENTIFYING HIS NAME OR COMPANY. |
| | 6-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| | AHU. SPECIFY ALL CONNECTORS. SECTION |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 7-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 SBC 1997. |
| | 8-REVISE THE ROOF SHEATHING SPECS ON TYP |
| | WALL SECTION. SEE SECTION 2306 OF CITY |
| | AMENDMENTS TO SBC 1997. |
| | 9-SOIL TEST REPORT ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | 10-REVISE SIZE OF WINDOW BEDROOM #3. |
| | 24SH WINDOW DOESN'T PROVIDE THE 24" |
| | MIN. CLEAR HEIGHT REQUIREMENT OF |
| | SECTION 1005.4 SBC 1997. |