| 2001-11-28 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE AO: NEED TO PROVIDE THE |
| | ELEVATION CERTIFICATE. |
| | 2-REVISE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA IS INCORRECT. SEE |
| | SECTION 604.1.A.1 OF FLORIDA ENERGY |
| | EFFICIENCE CODE FOR BUILDING CONSTR. |
| | 3-PROVIDE CURRENT UL ASSEMBLY # FOR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | 4-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| | ENTRY DOORS. |
| | 5-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| | AHU. SPECIFY ALL CONNECTORS. |
| | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| | 6-REVISE WINDOW SIZE FOR BEDROOM #3. |
| | 24 SH WINDOW DOESN'T MEET THE MINIMUM |
| | CLEAR HT. OPENING OF 24". SEC 1005.4 |
| | 7-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS. |
| | 8-TRUSS DRAWINGS: |
| | -UPDATE GENERAL DETAILS. USE ASCE 7-95 |
| | FOR 140MPH OR SBC 1997 FOR 110MPH. |
| | -MAKE SURE ALL DETAILS ARE LEGIBLE. |
| | -REVIEW STAMP BY ENGINEER OF RECORD |
| | DOESN'T IDENTIFY THE FIRM WHO REVIEWED |
| | THE TRUSS DRAWINGS. |
| | NOTE: ENGINEER DOESN'T NEED TO SEAL |
| | THE TRUSS LAYOUT. ONLY REVIEW |
| | AKNOWLEDGMENT IS REQUIRED. |
| | 9-SOIL TEST REPORT ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE, NOT RUBBER STAMP, |
| | AS REQUIRED BY CHAPTER 471 FL STATUTES |
| | 10-TYPICAL WALL SECTION: REVISE ROOF |
| | SHEATHING SPECS. SEE SECTION 2306 OF |
| | CITY AMENDMENTS TO SBC FOR MINIMUM |
| | NAILING AND SPACING. |