| Plan Review Notes For Permit 01101352 |
| Permit Number |
01101352 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-29 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE AIC RATINGS FROM | | | FIRST REVIEW, HAS NOT BEEN SUBMITTED. | | | 110-9/215-5 | | | PLEASE SUBMIT THE RATING. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS | | | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | | | | 3)NOTE: PLEASE NOTE THAT PER | | | CONVERSATION WITH THE ELECTRICAL | | | INSPECTOR THERE | | | IS ALSO OTHER WORK ON SITE AND NEEDS TO | | | BE SHOWN. | | | | | | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS OVERHEAD SERVICE AND APPL SAYS | | | UNDERGROUND.?? PLEASE CALRIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|