Plan Review Notes
Plan Review Notes For Permit 01101346
Permit Number 01101346
Review Stop P
Sequence Number 2
Notes
Date Text
2001-11-01 00:00:00DENIED
 REFERENCE: SGC-97
  
 1) COMMENT #1 FROM PREVIOUS REVIEW NOT
 ADDRESSED. 2 COPIES OF SIGNED AND SEALED
 PLANS REQUIRED. PLANS NOT SEALED.
 2) CONFLICTING INFORMATION ON SHEETS.
 ONE SHEET SHOWS 54,000 BTUS (3 AT 18,000
 AND THE OTHER SHOWS 2 DRYERS AT 18,000
 AND THE 3RD AT 90,000. PLEASE CLARIFY.
 3) SEE GAS PERMIT APPLICATION REQUIRE-
 MENTS SHEET #'S 1- 5 & 9, INFORMATION
 STILL REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377