| Plan Review Notes For Permit 01101303 |
| Permit Number |
01101303 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-25 00:00:00 | ***************DENIED******************* | | | 1. LIFE SAFETY PLAN SHOWS RATED WALL AT | | | MECH RM, PROVIDE FIRE DAMPER LOCATION | | | IN DUCTS PER 1997 SMC 610.6 | | | 2. CLARIFY RATING AT DIFFUSERS RG-2 AND | | | CD-3 IN LOBBY. IS THIS A REQUIRED RATED | | | CEILING? IF SO SHOW WALL RATINGS FOR | | | DETERMINATION OF OPENING PROTECTION | | | REQUIRED AT OTHER DUCT LOCATIONS. NO | | | RATINGS ARE INDICATED ON LIFE SAFETY | | | DRAWING IN THIS AREA. |
|