Plan Review Notes
Plan Review Notes For Permit 01101303
Permit Number 01101303
Review Stop M
Sequence Number 2
Notes
Date Text
2002-03-25 00:00:00***************DENIED*******************
 1. LIFE SAFETY PLAN SHOWS RATED WALL AT
 MECH RM, PROVIDE FIRE DAMPER LOCATION
 IN DUCTS PER 1997 SMC 610.6
 2. CLARIFY RATING AT DIFFUSERS RG-2 AND
 CD-3 IN LOBBY. IS THIS A REQUIRED RATED
 CEILING? IF SO SHOW WALL RATINGS FOR
 DETERMINATION OF OPENING PROTECTION
 REQUIRED AT OTHER DUCT LOCATIONS. NO
 RATINGS ARE INDICATED ON LIFE SAFETY
 DRAWING IN THIS AREA.