2001-11-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101303
 720 39TH ST
 CITY PROJECT
 DAY CARE FACILITY
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 1)- DROP OFF SITE: FL ACC CODE 4.3.2
 ACCESSIBLE ROUTE, CURB CUTS. THE SITE
 DOESN'T INDICATE PARKING?
  
 2)- FL ACC CODE : PLANS DO NOT DESIGNATE
 WHICH RESROOMS ARE TO BE HANDICAPPED
 ACCESIBLE?
  
 3)- PORCH 123 SHEET S-1 INDICATES MW-1
 A 8" CMU, VERSES A-2 1'-0" THICK.
  
 4)- S-1 THE COMMON WALL BETWEEN ROOM 117
 & HALLWAY 107 INDICATES THIS TO BE
 A BEARING MASONARY WALL, MISSING
 VERTICAL SUPPORT?
  
 5)- S-1, S-2 LINTAL INFORMATIOIN MISSING
 S-3 CONCRETE LINTALS NOTE "A" INDICATES
 THERE MAY BE DROP BEAM OR LINTALS?
  
 6)- MISSING MINIMUM BEARING, SOILS
 REPORT.
  
 7)- SBC 1606.6.2.6COMPONENTS& CLADDING
 THE CITY REQUIRES PRODUCT TESTING
 REPORTS FOR ALL GLAZED OPENINGS:
 WINDOWS
 FRENCH DOORS( IF DOOR ARE CONNENCTED
 WITH SIDE LITES TESTING
 IS TO INDICATE THIS,
 ALSO IF TRANSOMS ARE
 TO BE USED.
 WINDOW MULLIONS
 ROOFING ASSEMBLIES
 STORM SHUTTERS
 GLAZED OPENINGS REQUIRE PRODUCT TESTING
 FOR LARGE MISSLE IMPACT RESISTANCE
 TESTING. IF WINDOWS HAVEN'T RECEIVED
 THIS CERTIFICATION STORM SHUTTERS PASS-
 ING THIS TEST MAY BE SUBMITTED.
  
 8)- COUNTY IMPACT FEES TO BE PAID TO THE
 COUNTY BEFOR ISSUANCE.
  
 PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412