| Plan Review Notes For Permit 01101295 |
| Permit Number |
01101295 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-25 00:00:00 | ***************DENIED******************* | | | | | | 1. OUTSIDE AIR CALCULATIONS FOR | | | GYMNASIUM AREA NEEDS TO BE 20 CFM PER | | | PER PER ASHRAE 62-89 TABLE 2 | | | 2. FIRE DAMPER LOCATIONS SHALL BE | | | INDICATED ON PLANS BY THE DESIGN | | | PROFESSIONAL PER 1997 SMC 610.6 | | | 3. PROVIDE TWO SETS OF RAISED SEAL, | | | SIGNED DRAWINGS FOR REVIEW | | | 4. CONDENSING UNITS ON ROOF SHALL BE ON | | | APPROVED STANDS MINIMUM 18" CLEARANCE | | | BETWEEN ROOF STRUCTURE AND BOTTOM OF | | | STAND SUPPORT. SUBMIT STAND DETAIL | | | INCLUDING ROOF ATTACHMENT AND ANCHOR | | | METHOD FOR UNITS. |
|