| Plan Review Notes For Permit 01101295 |
| Permit Number |
01101295 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-25 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW. - SHT A2-1 REST | | | ROOMS #118, #126 H/C STALL TO COMPLY FIG | | | 30(E) SIZE, LAYOUT, CLEAR FLOOR SPACE, | | | DOOR SWING SEC 4.22.2(1). | | | 2) FROM PREVIOUS REVIEW. - SHT P1,2,3 | | | SEC 303 MATERIALS FOR DRAIN, WASTE, & | | | VENT. WATER PIPE AND RAIN WATER LEADERS. | | | 3) FROM PREVIOUS REVIEW. - SHT P1,3 PLBG | | | NOTE (5) WHA, LOCATION, PLACEMENT AS PER | | | MFG INSTRUCTIONS, NOT AT THE HIGH POINT | | | OF SYSTEM. 607.8.2 | | | 4) FROM PREVIOUS REVIEW. - SHT P1 PLBG | | | NOTE (9) AND DETAIL FOR THE WATER HEATER | | | CONFLICT? SEC 104.3 | | | 5) FROM PREVIOUS REVIEW. - SHT P2 PUBLIC | | | REST RM'S #119, #121 FLOOR DRAINS REQUIR | | | ED, SEC 409.4 | | | 6) FROM PREVIOUS REVIEW. - SHT A3, P2 | | | PROVIDE CALCULATIONS FOR ROOF DRAINS, | | | OVERFLOW DRAINS. 1/2 VERTICAL WALLS, | | | DRAIN TERMINATION, PIPE SIZE. SEC 1108, | | | 1108.3, 1109 | | | 7) SHT M4 HUB DRAIN FOR CONDENSATE NOT | | | APPROVED. ALL INDIRECT WASTE SHALL DRAIN | | | TO AN APPROVED RECEPTOR, FLOOR SINK. | | | SEC 804.5 | | | 8) SHT P2 CONDENSATE LINE SHALL HAVE A | | | RELIEF VENT INSTALLED AS CONDENSATE LINE | | | EXITS BLDG AND TERMINATE 6" ABOVE GRADE | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|