Plan Review Notes
Plan Review Notes For Permit 01101295
Permit Number 01101295
Review Stop P
Sequence Number 2
Notes
Date Text
2002-03-25 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEW. - SHT A2-1 REST
 ROOMS #118, #126 H/C STALL TO COMPLY FIG
 30(E) SIZE, LAYOUT, CLEAR FLOOR SPACE,
 DOOR SWING SEC 4.22.2(1).
 2) FROM PREVIOUS REVIEW. - SHT P1,2,3
 SEC 303 MATERIALS FOR DRAIN, WASTE, &
 VENT. WATER PIPE AND RAIN WATER LEADERS.
 3) FROM PREVIOUS REVIEW. - SHT P1,3 PLBG
 NOTE (5) WHA, LOCATION, PLACEMENT AS PER
 MFG INSTRUCTIONS, NOT AT THE HIGH POINT
 OF SYSTEM. 607.8.2
 4) FROM PREVIOUS REVIEW. - SHT P1 PLBG
 NOTE (9) AND DETAIL FOR THE WATER HEATER
 CONFLICT? SEC 104.3
 5) FROM PREVIOUS REVIEW. - SHT P2 PUBLIC
 REST RM'S #119, #121 FLOOR DRAINS REQUIR
 ED, SEC 409.4
 6) FROM PREVIOUS REVIEW. - SHT A3, P2
 PROVIDE CALCULATIONS FOR ROOF DRAINS,
 OVERFLOW DRAINS. 1/2 VERTICAL WALLS,
 DRAIN TERMINATION, PIPE SIZE. SEC 1108,
 1108.3, 1109
 7) SHT M4 HUB DRAIN FOR CONDENSATE NOT
 APPROVED. ALL INDIRECT WASTE SHALL DRAIN
 TO AN APPROVED RECEPTOR, FLOOR SINK.
 SEC 804.5
 8) SHT P2 CONDENSATE LINE SHALL HAVE A
 RELIEF VENT INSTALLED AS CONDENSATE LINE
 EXITS BLDG AND TERMINATE 6" ABOVE GRADE
  
 REVIEW BY KEN STEVENS