Plan Review Notes
Plan Review Notes For Permit 01101295
Permit Number 01101295
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-11 00:00:00PLUMBING PLAN REVIEW, DENIED
 CODE REFERENCE STD PLBG CODE-94
 STANDARD MECHANICAL CODE-97
 FLORIDA ACCESSIBILITY CODE-97
 (1A) SHT A2-1 REST RM'S #118,#126 H/C
 STALL TO COMPLY FIG 30(E) SIZE, LAYOUT.
 DOOR SWING SEC 4.22.2(1).
 (1B) ENTRY TO MEN & WOMENS REST RM'S TO
 COMPLY W/SEC 4.13.6 & FIG. 25 DOOR SWING
 (2) SHT P1,2,3 SEC 303 MATERIALS, LIST
 TYPES OF MATERIALS FOR DRAIN WASTE,VENT.
 WATER PIPE AND RAIN WATER LEADERS.
 (3)SHT P1,3 PLBG NOTE (5) WHA, LOCATION,
 PLACEMENT AS PER MFG INSTRUCTIONS, NOT
 AT THE HIGH POINT OF SYSTEM.607.8.2
 (4) SHT P1,PLBG NOTE (9) AND DETAIL FOR
 THE WATER HEATER, CONFLICT? SEC 104.3
 (5) SHT P1 PLBG NOTE (10) TYPE OF BACK
 FLOW PREVENTER SHALL BE A RPZV SEC 606.
 (6) SHT P2 PUBLIC REST RM'S #119.#121
 FLR DRAINS REQUIRED, SEC 409.4
 (7) SHT A3,P2PROVIDE CALCULATIONS FOR
 ROOF DRAINS,OVERFLO DRAINS, 1/2 VERTICAL
 WALLS, DRAIN TERMINATION, PIPE SIZES.
 SEC 1108,1108.3, 1109
 (8) SHT A3,RTU UNITS,SHOW TERMINATION OF
 A/C CONDENSATE.SMC-97,SEC 304.8.3
 (9) SHT M3, MECHANICAL RM #111,#117,
 REFERENCE TO LARGE SCALE MECHANICAL PLAN
 SHT M-4,NOT INCLUDED, SHOW THE TERMIN-
 ATION OF AHU A/C CONDENSATE SEC 304.8.3
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233