| 2001-11-11 00:00:00 | PLUMBING PLAN REVIEW, DENIED |
| | CODE REFERENCE STD PLBG CODE-94 |
| | STANDARD MECHANICAL CODE-97 |
| | FLORIDA ACCESSIBILITY CODE-97 |
| | (1A) SHT A2-1 REST RM'S #118,#126 H/C |
| | STALL TO COMPLY FIG 30(E) SIZE, LAYOUT. |
| | DOOR SWING SEC 4.22.2(1). |
| | (1B) ENTRY TO MEN & WOMENS REST RM'S TO |
| | COMPLY W/SEC 4.13.6 & FIG. 25 DOOR SWING |
| | (2) SHT P1,2,3 SEC 303 MATERIALS, LIST |
| | TYPES OF MATERIALS FOR DRAIN WASTE,VENT. |
| | WATER PIPE AND RAIN WATER LEADERS. |
| | (3)SHT P1,3 PLBG NOTE (5) WHA, LOCATION, |
| | PLACEMENT AS PER MFG INSTRUCTIONS, NOT |
| | AT THE HIGH POINT OF SYSTEM.607.8.2 |
| | (4) SHT P1,PLBG NOTE (9) AND DETAIL FOR |
| | THE WATER HEATER, CONFLICT? SEC 104.3 |
| | (5) SHT P1 PLBG NOTE (10) TYPE OF BACK |
| | FLOW PREVENTER SHALL BE A RPZV SEC 606. |
| | (6) SHT P2 PUBLIC REST RM'S #119.#121 |
| | FLR DRAINS REQUIRED, SEC 409.4 |
| | (7) SHT A3,P2PROVIDE CALCULATIONS FOR |
| | ROOF DRAINS,OVERFLO DRAINS, 1/2 VERTICAL |
| | WALLS, DRAIN TERMINATION, PIPE SIZES. |
| | SEC 1108,1108.3, 1109 |
| | (8) SHT A3,RTU UNITS,SHOW TERMINATION OF |
| | A/C CONDENSATE.SMC-97,SEC 304.8.3 |
| | (9) SHT M3, MECHANICAL RM #111,#117, |
| | REFERENCE TO LARGE SCALE MECHANICAL PLAN |
| | SHT M-4,NOT INCLUDED, SHOW THE TERMIN- |
| | ATION OF AHU A/C CONDENSATE SEC 304.8.3 |
| | END OF COMMENTS PAUL SCHMITZ |