| Plan Review Notes For Permit 01101295 |
| Permit Number |
01101295 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-05 00:00:00 | ********************DENIED************** | | | | | | | | | PLAN SHEET LS1 NOTE #2, INDICATES 1 HR | | | FIRE RATED PARTITION AT MECH ROOMS 111, | | | 113, & 119.PLANS REFLECT MECH ROOMS | | | AS 111 AND 127.PLEASE CORRALATE PLANS | | | WITH PLAN NOTES. | | | | | | FIRE DAMPERS ARE NOT INDICATED ON PLANS. | | | PLEASE IDENTIFY ALL FIRE DAMPERS AND | | | ACCESS DOORS TO FIRE DAMPERS ON THE | | | PLAN SHEET. | | | | | | IF YOU HAVE ANY QUESTIONS. PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|