Plan Review Notes
Plan Review Notes For Permit 01101295
Permit Number 01101295
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-23 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE INDICATE FIRE HYDRANT
 LOCATIONS ON SITE PLAN.
 3) NO FIRE SPRINKLER PLANS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 4) PLEASE PROVIDE MORE DETAILS ON
 BLEACHERS PLANNED FOR USE.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 6) A SMOKE DETECTOR IS REQUIRED ABOVE
 FIRE ALARM CONTROL PANEL, HALL 105.
 ALSO A REMOTE ANNUNCIATOR WILL
 BE REQUIRED BECAUSE THE EAST ENTRY
 PORCH MAY NOT BE FIRE RESCUE POINT
 OF ENTRY.
 7) COULD NOT LOCATE KNOX-BOX.
 8) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 9) ANY COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS IN CONCESSION AREA
 TO HAVE AN APPROVED HOOD,DUCT,AND
 EXTINGUISHING SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910