2001-11-14 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK# 01101295
 4017 PINEWOOD AV
 CITY PROJECT "GYMNASIUM"
 TEL: (561) 848-1988
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 **** PLANS SUBMITTED AFTER JAN. 1,2002
 FOR PERMIT APPLICATION WILL BE REVIEWED
 UNDER THE 2001 FLORIDA CODE.******
  
 1)- SBC 104.2.2 ADD INFORMATION REQUIRED
 A CURRENT SURVEY INDICATE THE PROPOSED
 LOCATION OF BUILDING ON SURVEY FOR TABLE
 600 ISSUES.
  
 2)- SBC 1804.2.7.2(3) SOILS REPORT/ WITH
 THE MINIMUM SOIL BEARING VALUE.
  
 3)- ENERGY CALCULATIONS WITH MANUAL "J"
  
 4)- A SITE PLAN WITH HANDICAPPED INDICA-
 TING AN ACCESSIBLE ROUTE FROM CURB FOR
 (PUBLIC TRANSPORTATION) AND FROM THE
 HANDICAPPED PARKING SPACES.
 INDICATE WHAT AREAS ARE TO BE ACCESS
 IBLE, FOR AXAMPLE FROM THE EXTERIOR
 HANDICAPPED RESTROOMS TO THE RECEPTION
 AREA DO YOU GO BACK OUT TO THE CITY SIDE
 WALKS OR ARE THERE OTHER EGRESS PATHS
 NOT INDICATED?
  
 5)- S.S.553.79.(5A) THIS BUILDING
 QUALIFIES AS A THRESHOLD BUILDING.
 THE OCCUPANT LOAD OF THE GYM, 704 PEOPLE
 QUALIFIES THIS BUILDING AS A THRESHOLD
 BUILDING.
 A) A THRESHOLD INSPECTION PLAN WILL
 BE REQUIRED TO BE FILED WITH THE
 BUILDING DEPARTMENT. THE ENFORC-
 ING AGENCY SHALL REQUIRE A SPEC-
 IAL INSPECTOR TO PREFORM STRUCTUR
 AL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO AND APPROVED
 BY THE ENFORCING AGENCY PRIOR TO
 THE ISSUANCE OF THE PERMIT FOR
 THE CONSTRUCTION OF THE THRESHOLD
 BUILDING.
 B)- THE THRESHOLD INSPECTOR SHALL
 MEET WITH ASSISTANT BUILDING OFF-
 ICAL DON NEELY FOR APPROVAL.
 C)- (3) SETS OF PLANS WILLBE REQUIRED
 FOR THE PERMITED SET.
  
 5)- MISSINGINFORMATION, THE MINIMUM
 BUILDING TYPE FOR OCCUPANCY SMALL ASSEM-
 BLY? SEE SBC TABLE 500, SPRINKLERED/
 PROTECTED?SQ. FT. UNDER ROOF NOT GIVEN
  
 6)- SBC 104.2.2.ADDITIONAL INFORMATIOIN,
 SBC TABLE 600 PROPERTY LINE CAN NOT BE
 ESTABLISHED, NO SURVEY, TABLE 600 % OF
 OPENINGS MAY BE AN ISSUE.
  
 7)- FOOTING SCHEDULE- MISSING T.E.-1
 ON FOOTING SCHEDULE, THERE IS A THICKEN
 EDGE SECTION ON S-4 WHICH IS TO BE USED?
 ONE IS 12" THE THER 16" VERTICALLY?
  
 8)- MISSING IS INFORMATIONM FOR MC1/MC2
 2103.1 ENGINEERED MASONARY DESIGN SHALL
 COMPLY WITH ASCE 530- COLUMNS 5.6.1.4
 VERTICAL COLUMNS MINIMUM NUMBER OF BARS
 SHALL BE FOUR.
  
 9)- SBC TABLE 1606. IMPORTANCE FACTOR OF
 1.15 TO BE A USE FACTOR, OCCUPANT LOAD
 =>300.
  
 10)-SBC 1606.2.6.2 COMPONENTS & CLADDING
 (3) PRODUCT APPROVAL REPORTS WILL BE RE-
 QUIRED FOR THE FOLLOWING ITEMS:
 A) EXTERIOR WINDOWS
 B) EXTERIOR DOORS
 C) ROLL UP OR GARAGE OVERHEAD DOORS
 D) SKYLIGHTS
 E) ROFFING ASSEMBLIES
  
 THE PLANS ARE LACKING SUFFICIENT INFORMA
 TION TO DO A THOROUGH PLAN REVIEW AT
 THIS TIME. THE QUESTIONS RAISED UNDER
 THIS REVIEW WILL RAISE ADDITIONAL
 QUESTIONS NOT ABLE TO BE ANSWER PRESENT-
 LY.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412