| Notes |
| Date |
Text |
| 2001-12-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101293 | | | 400 NORTHPOINT PKWAY / 403 | | | BUTTERS CONSSTRUCTION | | | CONTACT: FRANK GAMBENO | | | TEL: (954) 570-8111 | | | FAX: (954) 570-8844 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- PLANS INDICATE A MERCANTILE OCCUPAN- | | | CY.THE AMOUNT OF FLAMMABLE/ COMBUSTIBLE | | | LIQUIDS EXCEEDS THE AMOUNTS ALLLOWABLE | | | IN TABLE 308.2B, FOR SPRINKLERED BUILD- | | | ING, NOT IN A CABINET. | | | THE TYPE OCCUPANCY SHALL BE A "H2 OCCU- | | | PANCY" DEFLAGRATION HAZARDS, CLASS I, | | | II AND III-A FLAMMABLE OR COMBUSTIBLE | | | LIQUIDS. | | | | | | 2)- 408.6 STORAGE OF HAZARDOUS PRODUC- | | | TION MATERIAL | | | ROOMS USED TO THE STORAGE OF HPM IN QUAN | | | ITIES GREATER THAN SET FORTH IN TABLE | | | 408.3.3.B EXCEPT FOR THE PERMITTED | | | WITHIN A FABRICATION AREA, SHALL COMPLY | | | WITH THE PROVISIONS OF NFPA 30 PROVIDED | | | THAT THE AREA OF AN HPM CUTOFF ROOM | | | SHALL NOT EXCEED 6,000 SQ. FT. | | | | | | TO COMPLY WITH SECTIONS 408.6.1-408.6.7 | | | | | | SEE NFPA 30 FOR ADDITIONAL INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|