| 2001-11-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01101293 |
| | 400 NORTHPOINT # 403 |
| | CONT: BUTTERS CONT |
| | (954) 570-8111 |
| | |
| | SBC= STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- TO BE ABLE TO IDENTIFY THE TYPE OF |
| | BUILDING OCCUPANCY, THE CITY REQUEST |
| | ADDITIONAL INFORMATION, MSDS SHEETS FOR |
| | THE VARIOUS CHEMICALS PAINTS, THINNERS, |
| | SOLVENTS, THE QUANITIES OF EACH. DEPEND- |
| | ING ON THIS INFORMATION AND SBC TABLE |
| | 308.B THE CITY WILL BE ABLE TO DETERMINE |
| | THE OCCUPANCY CLASS. |
| | WILL THIS SPACE BE FIRE SPRINKLERED. |
| | PLANS INDICATE THAT IT WILL BE SUBMIT |
| | FIRE SPRINKLER LAYOUT, DROPPED CEILING |
| | AREA INDICATE FIRE SPRINKLERS. |
| | |
| | 2)- WILL THE AREA ABOVE THE OFFICE SPACE |
| | BE USED FOR STORAGE. |
| | |
| | 3)- WAREHOUSE (STORAGE AREA 108) HOW |
| | WILL THE RAW AND FINISHED PRODUCT BE |
| | STORED? HEIGHT OF RACKS?CLEAR HEIGTH |
| | BETWEEN THE RACK AREA FOR STORAGE & |
| | THE BOTTOM OF SPRINKLER HEAD? |
| | |
| | 4)- MIXING ROOM DETAIL "C", THIS DETAIL |
| | INDICATES A LIQUID TIGHT CURB ON ALL 4 |
| | SIDES OF THE ROOM, WILL THE CURB RUN |
| | ALSO UNDERNEATH THE DOORWAYS? WHAT MATER |
| | IAL WILL BE USED TO SEAL THE FLOOR AND |
| | CURB? HOW WILL SPILLAGE BE REMOVED? |
| | |
| | BUILDING PLAN REVIEW |