| 2002-06-26 00:00:00 | REFERENCE RESPONSE LETTER DATED JUNE |
| | 12, 2002. |
| | |
| | RESPONSE TO COMMENT #1: A 2 HR ENCLOSURE |
| | WILL BE PROVIDED.SEE ARCHITECTURAL |
| | PLANS SHEET A-6.02 FOR 2 HR ENCLOSURE. |
| | |
| | PLAN SHEET A-6.02-INDICATE STAIR RISER |
| | & STAIR DETAIL, NO 2 HR ENCLOSURE |
| | SHOWN.PLEASE REVISE MECHANICAL PLANS |
| | WITH ANOTE INDICATING DUCT TO BE IN A |
| | RATED SHAFT PLEASE PROVIDE HR RATING. |
| | PLEASE REMOVE FIRE DAMPERS ON DUCT |
| | THAT IS TO BE IN THE SHAFT. |
| | |
| | RESPONSE TO COMMENT 2B: A DRYER BOOSTER |
| | FAN HAS BEEN ADDED TO ALL DRYERS. |
| | |
| | PLEASE NOTE SHOULD THE BOOSTER FAN BE |
| | USED ON THE DRYER EXHAUST A MEANS OF |
| | NOTIFICATION TO THE OWNER/TENANT WILL |
| | BE REQUIRED SHOULD THE BOOSTER FAN |
| | FAIL. |
| | |
| | RESPONSE TO COMMENT #4: AXUILIARY DRAIN |
| | PANS WILL BE PROVIDED FOR ALL HORIZONTAL |
| | HEAT PUMPS. SEE INSTALLATION DETAILS ON |
| | SHEET AC-6. |
| | |
| | INDICATE ON THE PLAN WHAT WILL SERVE |
| | AS PROTECTION FOR THE VERTICAL UNITS |
| | SHOULD THE PRIMARY DRAIN BE RESTRICTED |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |