| 2002-07-25 00:00:00 | THIS IS THE THIRD REQUEST FOR ATTACHMENT |
| | DETAILS FOR THE CAST STONE TO BE |
| | APPLIED TO THE BUILDING.THE ARCHITECT |
| | HAS REPRODUCED CODE TEXT ON SHEET A4.02 |
| | (SBC 1403.2.6)THIS IS NOT SPECIFIC |
| | DESIGN INFORMATION.SEE SBC 104.2.1 |
| | REGARDING THE PROHIBITION OF CITING THE |
| | CODE IN LIEU OF SPECIFIC DESIGN |
| | INFORMATION.THIS CAVEAT WAS NOTED ON |
| | PREVIOUS APPLICATION REJECTIONS ALSO. |
| | |
| | THIS IS THE THIRD REQUEST FOR |
| | INFORMATION ON THE SPRINKLER HEADS THAT |
| | WILL PROVIDE EQUIVALENT PROTECTION FOR |
| | FIRE RATED OPENING PROTECTIVES. |
| | |
| | SHEET SP8, PREPARED BY ALBERT SHUB, PE |
| | SHOWS A "WS VERTICAL CENTRAL" HEAD AT |
| | "EXTERIOR WALL & INTERIOR OF FIXED |
| | GLASS" AND "AT EXTERIOR WALL & INTERIOR |
| | OF SLIDING GLASS DOORS". |
| | |
| | THERE IS NOTHING MORE ON THE FIRE |
| | PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | THAT ADDRESSES THIS SPECIAL APPLICATION |
| | WINDOW SPRINKLER. |
| | |
| | THE CENTRAL, WS, 3-01, MODEL WS SPECIFIC |
| | APPLICATION WINDOW SPRINKLERS TYCO FIRE |
| | PRODUCTS, TECHNICAL DATA SHEET #6-2.0 |
| | PRINTED 3/01 CONTAINS THE FOLLOWING |
| | INFORMATION. |
| | |
| | UNDER GENERAL DESCRIPTION IT STATES THAT |
| | THE WS HEAD CAN BE USED AS INTERIOR |
| | PROTECTION OF GLAZING.IT GOES ON TO |
| | ALLOW THE USE OF THE HEAD AS AN "OPEN" |
| | SPRINKLER FOR EXTERIOR APPLICATIONS, |
| | AND USING THE DESIGN REQUIREMENTS OF |
| | NFPA.THE ENGINEERED DESIGN DOCUMENTS |
| | DO NOT ADDRESS THIS. |
| | |
| | UNDER "WARNING" IN THE SAME CENTRAL TECH |
| | DATA IT SAYS THE HEAD MUST BE INSTALLED |
| | & MAINTAINED ISN COMPLIANCE WITH THE |
| | DATA SHEET, NFPA, AND ANY OTHER |
| | APPLICABLE STANDARDS.CHAPTER 4-7, |
| | NFPA13-99 OUTSIDE SPRINKLERS, SOME OF |
| | THE CRITERIA IS FOR AN INDEPENDENT |
| | CONTROL VALVE, CORROSION RESISTANCE AND |
| | A PRESSURE GAUGE.THESE ARE NOT |
| | INDICATED ON THE ENGINEERED DESIGN |
| | DOCUMENTS. |
| | |
| | THE CENTRAL WS TECH DATA UNDER "DESIGN |
| | CRITERIA" DECLARES THE HEADS TO BE OPEN |
| | SPRINKLERS FOR OUTSIDE USE. |
| | |
| | SAME CENTRAL WS TECH DATA SHEET UNDER |
| | "AREA OF USE" IT STATES THAT THE WS MAY |
| | BE USED TO PROTECT NON-OPERABLE WINDOWS. |
| | THE ENGINEERED DESIGN DOCUMENTS PROPOSE |
| | THE USE OF THE HEADS ON SLIDING GLASS |
| | DOORS, (OPERABLE), FOR INTERIOR AND |
| | EXTERIOR. |
| | |
| | SAME CENTRAL DATA SHEET UNDER "MINIMUM |
| | CLEARANCE FROM FACE OF GLASS TO |
| | COMBUSTIBLE MATERIALS" FOR THE USE OF A |
| | 36" PONY WALL OR SIMILAR METHOD. |
| | NOTHING SHOWN ON THE ENGINEERED DESIGN |
| | DOCUMENTS. |
| | |
| | SAME CENTRAL DATA SHEET UNDER |
| | RECOMMENDED HYDRAULIC REQUIREMENTS IS A |
| | SPECIFIC FORMULA THAT PROVIDES FOR AN |
| | INCREASED HYDRAULIC DEMAND TO BE |
| | ADDITIVE TO THE MOST DEMANDING |
| | HYDRAULIC DESIGN AREA.FURTHER THE |
| | OPEN EXTERIOR HEADS ARE CALCULATED AS A |
| | A DELUGE SYSTEM IN ACCORDANCE WITH NFPA. |
| | |
| | NER-516, NATIONAL EVALUATION REPORT FOR |
| | THIS PARTICULAR SPRINKLER HEAD, (A |
| | RECOGNIZED LISTING AGENCY) WAS SHARED |
| | WITH THE BUILDING DESIGNERS IN A |
| | MEETING PRIOR TO THE PREPARATION OF |
| | THESE DRAWINGS.THAT REPORT INVOKES |
| | THE CENTRAL DATA SHEET REFERENCED ABOVE. |
| | |
| | |
| | RULE 61G15-32.003 (4) COMMON |
| | REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. OF THE FLORIDA ADOMINSTRATIVE |
| | CODE READS IN PART:WHEN CODES AND |
| | STANDARDS ARE NOT AVAILABLE OR |
| | APPLICABLE, AND SAID LAYOUT DOCUMENTS |
| | ARE TO BE BASED ON ENGINEERING |
| | JUDGMENT, ANY REASONS AND ASSUMPTIONS |
| | MADE TO DEVELOP THE FIRE PROTECTION |
| | CONCEPT SHALL BE IDENTIFIED ON THE FIRE |
| | PROTECTION SYSTEM ENGINEERING |
| | DOCUMENTS. |
| | |
| | THE REASONS AND ASSUMPTIONS FOR THE |
| | DIVERSION FROM THE LISTING OF THE |
| | SPRINKLER ARE NOT READILY APPARENT ON |
| | THE FIRE PROTECTION SYSTEM ENGINEERING |
| | DOCUMENTS. |
| | |
| | THIS IS THE THIRD REQUEST FOR |
| | CALCULATIONS TO SUPPORT THE DESIGN OF |
| | THE PRESSURIZED STAIRS.A PARTIAL |
| | STATEMENT APPEARS ON SHEET AC 10 |
| | CONTAINS THE STATEMENT "STAIR SHALL BE |
| | PRESSURIZED TO 0.05" W.G. RELATIVE TO |
| | ATMOSPHERE, INCLUDING ANY STACK EFFECT |
| | FOR THE REST OF THE BUILDING." |
| | |
| | THIS STATEMENT IS SUGGESTIVE OF SBC 412. |
| | 11 (5) BUT DOES NOT ACCOMPLISH A |
| | DEMONSTRATION OF HOW THE DESIGN WAS |
| | ARRIVED AT. PLEASE PROVIDE CALCULATIONS |
| | DEMOSTRATING COMPLIANCE WITH SBC 412.11 |
| | (5) |
| | |
| | THE AC PLANS INDICATE FIRE DAMPERS FOR |
| | THE MISCELLANEOUS EQUIPMENT PENETRATING |
| | THE FIRE RATED WALL ON THE SOUTH SIDE |
| | OF THE BUILDING.SBC 705.1.3.1 |
| | REQUIRESLISTED DEVICES TO BE TESTED IN |
| | ACCORDANCE WITH NFPA 80 AND FIRE |
| | DAMPERS ARE TESTED TO UL 555, PLEASE |
| | ENSURE WITH NOTES, SPECIFICATIONS OR |
| | DETAILS THAT SBC 705.1.3.1 WILL BE |
| | COMPLIED WITH FOR ALL PENETRATIONS |
| | WHERE APPLICABLE. |
| | |
| | FL STATUTE 553.8(2)(B) MANDATES THE |
| | IMPOSITION OF A FEE FOR PLANS THAT ARE |
| | REJECTED THREE OR MORE TIMES FOR THE |
| | SAME CODE VIOLATION.A PRINTED COPY IS |
| | ATTACHED FOR USE. |