| Plan Review Notes For Permit 01101288 |
| Permit Number |
01101288 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-20 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA-24 CODE OF REGU- | | | LATION (CFR) 100.205 | | | (C)(IV) DESIGN MAN. | | | | | | 1) FROM PREVIOUS REVIEW, SHOW CLEAR | | | FLOOR SPACE FOR ALL BATHROOMS AND KIT. | | | FIXTURES PER DESIGN MANUAL. | | | 2) FROM PREVIOUS REVIEW, SHT L3.02,04. | | | COMMENT ASKED TO SHOW PREVENTER LOCATION | | | FOR WATER FEATURE, REPLY SAID NOTE WAS | | | ADDED. PLEASE SHOW WHERE BACKFLOW WILL | | | BE LOCATED. | | | 3) FROM PREVIOUS REVIEW, SHT P1,6 SHOW | | | LOCATION OF BACK FLOW PREVENTERS, UNABLE | | | TO FIND LOCATION FOR WATER FEATURES AND | | | COOLING TOWER. | | | 4) FROM PREVIOUS REVIEW SHT P-11 VERTI- | | | CAL SANITARY RISERS #5,#13 SEC 911 WET | | | VENTS, NO MORE THAN 4 FIXTURE UNITS ON A | | | 2" WET VENT. PLEASE RECHECK THESE RISERS | | | 5) SECONDARY ROOF DRAINS????????? |
|