| Plan Review Notes For Permit 01101288 |
| Permit Number |
01101288 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-03 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE REQUIRED | | | ON FIRE PROTECTION BACKFLOW DEVICES. | | | | | | 2) OCCUPANCY SEPARATIONS AND FIRE | | | RESISTANCE OF WALLS INDICATES A ONE HOUR | | | FIRE SEPARATION BETWEEN THE GARAGE AND | | | THE BUILDING. A TWO HOUR FIRE SEPARATION | | | IS REQUIRED. | | | | | | 3) SEVERAL DOORS INCLUDING EXIT DOORS | | | SWING OVER THE PROPERTY LINES FOR THE | | | BUILDING. | | | | | | 4) HOW DO THE EXIT DOORS THAT TERMINATE | | | ON THE SOUTH SIDE OF THE BUILDING INTO | | | THE ALLEY NOT BECOME OBSTRUCTED OR | | | BLOCKED. | | | | | | 5) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWING PAGE A4.02. | | | | | | 6) THE PLAN REVIEW COMMENTS OMITTED THAT | | | STAIRS ARE TO BE KEPT UP WITH | | | CONSTRUCTION. | | | | | | 7) ANY FIRE ALARM INITIATING DEVICE OR | | | FIRE SPRINKLER HEAD ACTIVATIONS ARE TO | | | INITIATE THE STAIRWELL PRESSURIZATION | | | FANS. | | | | | | 8) STAIR PRESSURIZATION IS 0.05 WATER | | | COLUMN TO INCLUDE MAXIMUM ANTICIPATED | | | STACK EFFECT FOR THE REST OF THE | | | BUILDING. | | | | | | 9) EIFS NOTED FOR BUILDING. PLEASE | | | REVIEW APPENDIX F OF THE STANDARD | | | BUILDING CODE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|