| 2002-04-15 00:00:00 | AS NOTED ON THE 11/16/02 LIST OF CODE |
| | COMMENTS, THE FLORIDA ACCESSIBILITY |
| | CODE FOR BUILDING CONSTRUCTION, SECTION |
| | 4.1.2 (5) REQUIRES SIX ACCESSIBLE |
| | SPACES, SECTION 4.6.3 OF THE FACBC |
| | REQUIRES |
| | THEM TO BE TWELVE FEET WIDE WITH AN |
| | ADJACENT FIVE FEET WIDE AISLE. PLEASE |
| | REVISE AS NECESSARY. |
| | |
| | THE DOOR SCHEDULES DO NOT SHOW THE RATED |
| | DOORS FOR THE ELEVATOR LOBBIES AS |
| | REQUIRED BY SBC 412.6.1.(20 MINUTES) |
| | |
| | THE 4TH LEVEL FLOOR PLAN ON SHEET A2.06, |
| | SHADED HATCHED AREA INDICATES A STEP AT |
| | THE DOOR FROM ELEVATOR LOBBY #1 TO THE |
| | SPA AREA.THIS IS PROHIBITED BY SBC |
| | 1012.1.3. |
| | |
| | SHEET A4.02 IS STILL MISSING |
| | INFORMATION FOR THE ATTACHMENT OF THE |
| | PRECAST CONCRETE.SEE SBC 1403.2. |
| | |
| | THE PLANS DEPICT THE USE OF"EIFS" TRIM |
| | IN VARIOUS PLACES.SBC F102.2.7 |
| | REQUIRES ARCHITECTURAL TRIM TO BE OF |
| | NON-COMBUSTIBLE OR FIRE RETARDANT |
| | TREATED WOOD. |
| | EIFS MEETS NEITHER OF THESE DESCRIPTIONS |
| | |
| | SHEET S19 INDICATES A COMBINATION OF |
| | WIND TUNNEL TESTING AND THE ANALYTICAL |
| | PROCEDURE.ASCE 7-95 SECTION 6.4.1.1 |
| | REQUIRES THATONLY ONE OF THE |
| | PROCEDURES BE USED. |
| | |
| | SHEET A6.01 SHOWS ROOF MOUNTED STAIR |
| | PRESSURIZATION FAN.AC-1 SHOWS A SUPPLY |
| | FAN AT THE LOBBY LEVEL.AC-6 SHOWS A |
| | 4650 CFM SUPPLYDUCT AND A 2500 CFM |
| | EXHAUST DUCT.PROVIDE CALCULATIONS AND |
| | A NARRATIVE DESCRIBING THE SEQUENCE OF |
| | OPERATION TO DEMONSTRATE COMPLIANCE WITH |
| | SBC 412.11 (5) AS PREVIOUSLY REQUESTED. |
| | |
| | PLEASE PROVIDE THE DATA FOR THE |
| | SPRINKLER HEADS THAT WILL PROVIDE AN |
| | "EQUIVALENT ALTERNATE" FOR FIRE RATED |
| | OPENING PROTECTIVES.SECTION 553.79 OF |
| | THE FLORIDA STATUTES REQUIRES THE FIRE |
| | PROTECTION INFORMATION TO BE ON THE |
| | PERMIT PLANS AS WELL AS SBC 104.2 AND |
| | NFPA 13 CHAPTER 6, (OR 8 IN THE 1999 |
| | EDITION) |