| 2003-07-21 00:00:00 | DENIED |
| | REFERENCE: SPC-94 |
| | FACBC-97 |
| | FHA-AMEND 98 DESIGN MANUAL |
| | |
| | 1) SHT P-1 NOT SIGNED, SEALED, & DATED. |
| | 2) SHT P-1A IS THIS A REVISION FOR ALL |
| | TYPICAL "B" UNITS OR FOR A SPECIFIC UNIT |
| | 3) SHT P-4 NOT SIGNED, SEALED, & DATED. |
| | 4) SHT P-7 NOT SIGNED, SEALED, & DATED. |
| | 5) SHT P-7A NOT SIGNED, SEALED, & DATED. |
| | 5) SHT P-7B NOT SIGNED, SEALED, & DATED. |
| | 6) SHT P-9 NOT SIGNED, SEALED, & DATED. |
| | 7) SHT P-10 NOT SIGNED, SEALED, & DATED. |
| | 8) SHT P-11 NOT SIGNED, SEALED, & DATED. |
| | 9) SHT P-11 OFFSETS FOR STACKS 1, 4, 5, |
| | 6, A RELIEF VENT FOR THE OFFSET SHALL BE |
| | INSTALLED AS PROVIDED IN CHAPTER 9 AND |
| | IN NO CASE SHALL A HORIZONTAL BRANCH |
| | CONNECT WITHIN THE OFFSET OR WITHIN 2FT |
| | ABOVE OR BELOW THE OFFSET. THE RELIEF |
| | VENTS SHALL COMPLY WITH SECTIONS 917, |
| | 917.1, 917.2 & 917.3. - SEC 715.4(4) |
| | 10) SHT P-11A NOT SIGNED, SEALED, & DAT- |
| | ED. RISERS #11, 13, & 18. OFFSET VENTS |
| | REQUIRED SEC. 917 & ALL SUBSECTIONS. EX- |
| | TRA FIXTURE UNITS NOT REFLECTED ON RISER |
| | DIAGRAM. |
| | 11) SHT P-12 RISERS 22, 23, 28, & 26 - |
| | OFFSET RELIEF VENTS REQUIRED PER SECTION |
| | 917. ALSO SEE SECTION 715.4(4). |
| | 12) SHT P-15 NOT SIGNED, SEALED, & DATED |
| | |