| Date |
Text |
| 2001-11-04 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | CODE REFERENCES,STD PLUMBING CODE-94. |
| | FAIR HOUSING ACT 24 CODE OF REGULATION, |
| | (CFR) 100.205 (C) (IV) DESIGN MANUAL. |
| | (1) SHT 8A.03 COMPLY WITH FHA CFR-24,AS |
| | LAID OUT IN THE DESIGN MANUAL, SPECIFY |
| | OPTION A OR B. REQUIRMENTS 1 THRU 7,SHOW |
| | MANEUVERING AND CLEAR FLOOR SPACE ALSO |
| | GRAB BAR REINFOFCEMENT/"DESIGN MANUAL". |
| | (2) SHT L3.02,04 DETAIL(11), WATER FEA- |
| | TURE, SHOW LOCATION OF REQUIRED BACK |
| | FLOW PREVENTER FOR WATER SUPPLY SEC 606 |
| | (3) SHT IR6.02,03,04 IRRIGATION WATER |
| | SUPPLY,BACK FLOW PREVENTER LOCATION. |
| | (4) SHT P1,6 SHOW LOCATION OF BACK FLOW |
| | PREVENTERS,FOR FLUSHING RING, COOLING |
| | TOWERS, WATER FEATURES, SWIMMING POOL, |
| | AND FOUNTAIN WATER SUPPLY,SEC 606. |
| | (5A SHT P9 AIR CHAMBERS, COMPLY WITH |
| | SEC 607.8.3, ACCESSIBLE AND RECHARGEABLE |
| | (B) WATER HAMMER ARRESTORS SEC 607.8.2 |
| | COMPLY WITH PDI-WH201,ASSE 1010, INSTALL |
| | PER MFG. FOR SIZE AND PLACEMENT. |
| | (6) SHT P9, NOTE(1) RP1-1 COMPLY WITH |
| | FL ENERGY CODE-97 SEC 412.1.ABCD.4 HOT |
| | WATER PIPING INSULATION TAB 4-11. |
| | (7) SHT P-10 RVD RISER DIAGRAM, COMPLY |
| | W/CITY OWPBMCW AMEND SPC-94,SEC507.6.1-2 |
| | 3/4"RVD DRAIN UP TO 150,000 BTU'S. |
| | PROVIDE CALCULATIONS FOR 3/4" RVD, SIZE. |
| | (8) SHT P-11 VERTIAL SANITARY RISERS,#1, |
| | #5,#13, SEC 911 WET VENTS, NO MORE THAN |
| | 4 FIXTURE UNITS ON A 2" WET VENT. |
| | (9) SHT P-12 VERTICAL SANITARY RISERS, |
| | #18,#21, SEC 916 RELIEF VENTS- STACKS OF |
| | 10 OR MORE BRANCH INTERVALS,REQUIRE |
| | RELIEF VENTS. |
| | (10) SHT P-13 DETAIL OF OIL INTERCEPTOR |
| | REFERENCE TO SFBC, CURRENT CODE SPC-94 |
| | SEC 1004.5, NOTE #19. |
| | (14) SHT P-13,SEC 104.3 EXAMINATION OF |
| | DOUCMENTS, PROVIDE SHOP DRAWINGS OF ALL |
| | PLUMBING FIXTURES AND EQUIPMENT. |
| | (15)SHT P-10 SEC 504 MINIMUM CAPICITY OF |
| | WATER HEATERS, COMPLY WITH TAB 505. |
| | (16) SHT A2.12,A7.02,SEC 1109 SECONDARY |
| | (EMERGENCY) SCUPPER DRAINS,PROVIDE CALCU |
| | LATIONS,INCLUDE 1/2 THE VERTICAL WALLS, |
| | SHOW SIZE AND LOCATION. |
| | END OF COMMENTSPAUL SCHMITZ |
| | QUESTIONS561-659- 8096X8233 |