| 2001-10-24 00:00:00 | 1) PLEASE BE ADVISED THAT THIS |
| | BUILDING WILL BE LOCATED IN THE CITY |
| | FIRE LIMITS. PLEASE BE ADVISED THAT |
| | CERTAIN RESTRICTIONS APPLY TO |
| | BUILDINGS LOCATED IN THESE LIMTS. |
| | PLEASE SEE APPENDIX F OF THE STANDARD |
| | BUILDING CODE AND CHAPTER 11 OF THE |
| | CITY CODE. |
| | 2) SEPARATION BETWEEN THE PARKING |
| | GARAGE AND OTHER PORTIONS OF THE |
| | BUILDING SHALL BE AT LEAST TWO HOURS |
| | AND NOT ONE HOUR AS DEPICTED. |
| | 3) WRONG LIFE SAFETY CODE REFERENCED |
| | ON THE PLANS. SHOULD READ 1985 EDITION |
| | INSTEAD OF 1997. |
| | 4) FIRE HYDRANTS NOT SHOWN ON DRAWINGS. |
| | 5) TEMPORARY STANDPIPES ARE REQUIRED |
| | DURING CONSTRUCTION WHEN THE BUILDING |
| | REACHES THREE STORIES AND FIFTY FEET |
| | IN HEIGHT. ALSO EXIT STAIRS ARE TO BE |
| | KEPT UP WITH CONSTRUCTION. |
| | 6) PLEASE INDICATE LOCATION ON KNOX-BOX. |
| | 7) PLEASE INDICATE COMPLIANCE WITH |
| | STRETCHER REQUIREMENTS OF THE STANDARD |
| | BUILDING CODE. |
| | 8) FIRE COMMAND ROOM SHALL CONTAIN |
| | ALL OF THE PRESCRIPTIVE REQUIREMENTS |
| | OF THE STANDARD BUILDING CODE. |
| | 9) PLEASE EXPLAIN PURPOSE OF GATES AT |
| | STAIRS ON THE ROOF. |
| | 10) PLEASE INDICATE ON THE PLANS THE |
| | NUMBER OF AIR CHANGES REQUIRED FOR THE |
| | CLOSED PARKING GARAGE. ALSO INDICATE |
| | AIR EXHAUST VOLUMES. |
| | 11) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 12) CANVAS CANOPIES TO BE FIRE |
| | RETARDANT. |
| | 13) PLEASE VERIFY THAT THE FIRE |
| | SPRINKLER HEADS PLANNED FOR USE ARE NOT |
| | ON THE VOLUNTARY RECALL LIST PROVIDED. |
| | 14) PLEASE INDICATE WHAT THE VOICE |
| | EVACUATION MESSAGE WILL SAY FOR THE |
| | FIRE ALARM SYSTEM. |
| | 15) PLEASE FURTHER EXPLAIN # 15 ON DOOR |
| | SCHEDULE NOTES. |
| | 16) HOW IS EXITING DIMINISHED WHEN THE |
| | GARAGE DOORS ARE CLOSED. |
| | 17) PLEASE INDICATE WHAT THE HANDRAILS |
| | AND GUARDRAILS RATED FOR. |
| | 18) PLEASE PROVIDE MORE INFORMATION ON |
| | THE INSULATION PLANNED FOR USE ON THE |
| | TRASH-CHUTE. |
| | 19) PLEASE EXPLAIN WHY NO FIRE SPRINKLER |
| | HEADS ARE SHOWN IN THE WALKWAY AREA. |
| | 20) NO PENETRATIONS ALLOWED IN THE |
| | STAIRWELLS EXCEPT FOR EMERGENCY LIGHTING |
| | AND FIRE PROTECTION SYSTEMS. |
| | 21) PLEASE DEMONSTRATE COMPLAINCE FOR |
| | SEPARATION OF EXITS. |
| | 22) PLEASE PROVIDE TESTING CRITERIA FOR |
| | THE STAIRWELL PRESSURIZATION EQUIPMENT |
| | CONTAINED WITHIN THE BUILDING. |
| | 23) FIRE SPRINKLER DRAWINGS HAVE FIRE |
| | COMMAND ROOM AND VALET ROOM SWITCHED. |
| | 24) CONDUIT SHAFTS ARE TO BE PROPERLY |
| | FIRE RATED. PLEASE INDICATE THIS ON |
| | THE PLANS. |
| | 25) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEMS AND FIRE |
| | ALARM SYSTEMS. |
| | 26) ELEVATORS TO COMPLY WITH ANSI A17.1. |
| | 27) HOW IS COMBUSTIBLE LINT REMOVED FROM |
| | DRYER EXHAUST VENTS. |
| | 28) ARE POOL CHEMICALS PLANNED TO BE |
| | STORED IN POOL EQUIPMENT ROOMS. |
| | 29) ANY CHANGES IN ELEVATIONS LESS THAN |
| | 21 INCHES SHALL BE BY RAMPS. |
| | 30) FIRST FLOOR RETAIL SPACES ARE TO |
| | MEET MINIMUM FIRE SAFETY REQUIREMENTS |
| | PRIOR TO BUILDING RECEIVING APPROVALS. |
| | 31) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | SMOKE CONTROL REQUIREMENTS FROM THE |
| | STANDARD BUILDING CODE. |
| | 32) WHAT WILL THE ACCESS PANEL DOOR |
| | BELOW THE MECHANICAL ROOM METAL |
| | ACCESS STAIR BE USED FOR. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |