| Plan Review Notes For Permit 01101258 |
| Permit Number |
01101258 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-11-13 00:00:00 | *******************PROVISO************** | | | | | | | | | 1.EQUIPMENT RACK ON ROOF SHALL BE A | | | MINIMUM OF 18"FOR ROOF SURFACE TO | | | BOTTOM OF SUPPORT RAIL.PLEASE | | | SUBMIT MANUFACTURER SUBMITTAL DATA | | | FOR REVIEW. | | | | | | 2.FIRE DAMPERS SHALL COMPLY WITH UL | | | 555 AND SHALL BEAR THE LABLE OF AN | | | APPROVED TESTING AGENCY. | | | | | | FIRE DAMPERS SHALL HAVE AN ACCESS | | | DOOR FOR PROPER MAINTENANCE AND | | | RESETTING (1997 SMC 610.5) | | | | | | 2 INSPECTIONS REQUIRED - | | | | | | FIRST WHEN DRYWALL AND FRAME | | | WORK IS INSTALLED. | | | SECOND WHEN ANGLE IS ATTACHED | | | TO DUCTWORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|