Plan Review Notes
Plan Review Notes For Permit 01101258
Permit Number 01101258
Review Stop M
Sequence Number 2
Notes
Date Text
2001-11-13 00:00:00*******************PROVISO**************
  
  
 1.EQUIPMENT RACK ON ROOF SHALL BE A
 MINIMUM OF 18"FOR ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.PLEASE
 SUBMIT MANUFACTURER SUBMITTAL DATA
 FOR REVIEW.
  
 2.FIRE DAMPERS SHALL COMPLY WITH UL
 555 AND SHALL BEAR THE LABLE OF AN
 APPROVED TESTING AGENCY.
  
 FIRE DAMPERS SHALL HAVE AN ACCESS
 DOOR FOR PROPER MAINTENANCE AND
 RESETTING (1997 SMC 610.5)
  
 2 INSPECTIONS REQUIRED -
  
 FIRST WHEN DRYWALL AND FRAME
 WORK IS INSTALLED.
 SECOND WHEN ANGLE IS ATTACHED
 TO DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.