Plan Review Notes
Plan Review Notes For Permit 01101258
Permit Number 01101258
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-25 00:00:00******************DENIED****************
  
  
 PLANS HAVE ENGINEER AND ARCHITECT TITLE
 BLOCKS WITH NO SEAL, SIGNATURE OR DATES
 AS REQUIRED BY FLORIDA STATUE (CHAPTER
 471).
  
 REVIEW NOTES FROM SUBMITTAL OF MASTER
 PERMIT 01060851
  
 1.PROVIDE LOCATION OF EXHAUST
 TERMINATION FOR THE FUME HOOD.
 TERMINATION SHALL COMPLY WITH 1997
 SMC 506.1, A MINIMUM OF 10' FROM
 ANY ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW, DOOR
 OR AIR INTAKE OPENING AND SHALL BE
 LOCATED AT LEAST 10' FROM ADJOINING
 GRADE LEVEL.
  
 2.PROVIDE INFORMATION ON EXHUAST FAN
 TO FUME HOOD.
  
 3.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.