| 2001-10-25 00:00:00 | ******************DENIED**************** | | | | | | | | | PLANS HAVE ENGINEER AND ARCHITECT TITLE | | | BLOCKS WITH NO SEAL, SIGNATURE OR DATES | | | AS REQUIRED BY FLORIDA STATUE (CHAPTER | | | 471). | | | | | | REVIEW NOTES FROM SUBMITTAL OF MASTER | | | PERMIT 01060851 | | | | | | 1.PROVIDE LOCATION OF EXHAUST | | | TERMINATION FOR THE FUME HOOD. | | | TERMINATION SHALL COMPLY WITH 1997 | | | SMC 506.1, A MINIMUM OF 10' FROM | | | ANY ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, DOOR | | | OR AIR INTAKE OPENING AND SHALL BE | | | LOCATED AT LEAST 10' FROM ADJOINING | | | GRADE LEVEL. | | | | | | 2.PROVIDE INFORMATION ON EXHUAST FAN | | | TO FUME HOOD. | | | | | | 3.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 501.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|