| 2002-08-14 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | ON THE PLANS AND RESUBMIT FOR REVIEW |
| | |
| | 1} THE REVISION SUBMITTED SHOWS THE |
| | METER MOVED OFF THE HOUSE TO A REMOTE |
| | LOCATION.PLEASE REDRAW THE RISER TO |
| | INDICATE THE TYPE OF GROUNDING SYSTEM |
| | AT THIS LOCATION,PLEASE NOTE THAT THE |
| | GEC SYSTEM IN 250-50 ARE AVAILABLE AND |
| | MUST BE USED AS INDICATED. |
| | |
| | 2} PLEASE CLARIFY THAT PANEL "B" IS |
| | STILL AN MLO AND BEING FED BACK FROM |
| | PANEL "A"? PLEASE NOTE BURIAL DEPTHS |
| | REQUIRE INSPECTIONS. |
| | |
| | 3} PANEL "A" MUST COMPLY WITH 230-70(A) |
| | NEC AND WEST PALM BEACH AMMENDMENTS, |
| | LOCATION OF DISCONNECT AT NEAREST POINT |
| | OF ENTRY,MAXIMUM OF 8' OF CONDUCTORS & |
| | NOT IN BATHROOM AS IT APPEARS ON THE |
| | DRAWING PLEASE CLARIFY. |
| | |
| | 4} INDICATE THE AIC RATING OF THE MAIN |
| | DISCONNECT PER 110-9 & 110-10. |
| | |
| | 5} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG.LIST SAME ON |
| | PANEL SCHEDULE. |
| | |
| | 6} NOTE THAT THE WATER HEATER IS LISTED |
| | @ 6000VA/240V ON THE CALC'S AND SHOWN |
| | AS 4AMPS/120V ON THE SCHEDULE, PLEASE |
| | CLARIFY. |
| | |
| | IF THERE ARE ANY QUESTIONS,PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |