| 2001-11-06 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - SGC-97 |
| | |
| | 1) PAGES A100 & P100 & P301. OUTSIDE |
| | SHOWER SHALL NOT HAVE A DRAIN. PLEASE |
| | REMOVE, NOT APPROVED PER UTILITY ORD. |
| | 2) PAGE A101 PLEASE PROVIDE ROOF DRAIN- |
| | AGE CALCULATIONS FOR PRIMARY AND SECOND- |
| | ARY DRAINS USING SPC SEC 1108 AND 1109. |
| | ADD 1/2 AREA OF VERTICAL WALLS/PARAPET |
| | WALLS PER 1108.3. ALSO ADD ANY AREA OF |
| | ROOFS THAT DRAIN ONTO NEW ROOFS. |
| | PLEASE SHOW DETAILS OF PRIMARY AND SEC- |
| | ONDARY DRAINS. - ALSO PLEASE SUPPLY |
| | CALCULATIONS FOR EXISTING ROOF - SHOW |
| | PRIMARY AND SECONDARY DRAINS WITH SIZES. |
| | 3) PAGE P300 DRYWELL DETAIL, OVERFLOW |
| | SHALL BE TIED INTO DRAIN LINE NOT DRY- |
| | WELL. |
| | 4) PAGE P300 WATER HEATER DETAIL, BOTTOM |
| | FED WATER HEATER SHALL HAVE A N36 VAC- |
| | BREAKER INSTALLED ON SUPPLY SIDE OF W/ |
| | HEATER. - EMERGENCY PAN DRAIN TO BE 1" |
| | 5) PAGE P300 INDIRECT WASTE FROM ICE |
| | MACHINE SHALL DRAIN INTO A FLOOR SINK |
| | NOT FLOOR DRAIN AS SHOWN. SPC SEC 804.5 |
| | 6) PAGE P300 WASHER DETAIL CLEAN OUT RE- |
| | QUIRED AT 4' AFF ON VENT STACK |
| | 7) PAGE P300 SEPARATE GAS PERMIT REQUIR- |
| | ED. SEE ATTACHED GAS PERMIT APPLICATION |
| | REQUIREMENT SHEET FOR FURTHER INFORMAT- |
| | ION REQUIRED. SUPPLY INFO FOR NUMBERS |
| | THAT ARE CIRCLED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |