Plan Review Notes
Plan Review Notes For Permit 01101224
Permit Number 01101224
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-06 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97
  
 1) PAGES A100 & P100 & P301. OUTSIDE
 SHOWER SHALL NOT HAVE A DRAIN. PLEASE
 REMOVE, NOT APPROVED PER UTILITY ORD.
 2) PAGE A101 PLEASE PROVIDE ROOF DRAIN-
 AGE CALCULATIONS FOR PRIMARY AND SECOND-
 ARY DRAINS USING SPC SEC 1108 AND 1109.
 ADD 1/2 AREA OF VERTICAL WALLS/PARAPET
 WALLS PER 1108.3. ALSO ADD ANY AREA OF
 ROOFS THAT DRAIN ONTO NEW ROOFS.
 PLEASE SHOW DETAILS OF PRIMARY AND SEC-
 ONDARY DRAINS. - ALSO PLEASE SUPPLY
 CALCULATIONS FOR EXISTING ROOF - SHOW
 PRIMARY AND SECONDARY DRAINS WITH SIZES.
 3) PAGE P300 DRYWELL DETAIL, OVERFLOW
 SHALL BE TIED INTO DRAIN LINE NOT DRY-
 WELL.
 4) PAGE P300 WATER HEATER DETAIL, BOTTOM
 FED WATER HEATER SHALL HAVE A N36 VAC-
 BREAKER INSTALLED ON SUPPLY SIDE OF W/
 HEATER. - EMERGENCY PAN DRAIN TO BE 1"
 5) PAGE P300 INDIRECT WASTE FROM ICE
 MACHINE SHALL DRAIN INTO A FLOOR SINK
 NOT FLOOR DRAIN AS SHOWN. SPC SEC 804.5
 6) PAGE P300 WASHER DETAIL CLEAN OUT RE-
 QUIRED AT 4' AFF ON VENT STACK
 7) PAGE P300 SEPARATE GAS PERMIT REQUIR-
 ED. SEE ATTACHED GAS PERMIT APPLICATION
 REQUIREMENT SHEET FOR FURTHER INFORMAT-
 ION REQUIRED. SUPPLY INFO FOR NUMBERS
 THAT ARE CIRCLED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377