| 2001-11-05 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PANELS ARE SHOWN AT 22,000, WHAT ABOUT |
| | MAIN? IS THE 22,000 FOR BREAKERS IN |
| | PANELS ALSO? |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | NOTE; MISSING IN BEDROOM #3 ALSO, SD |
| | SHOWN NEAR KITCHEN DOOR NEEDS TO BE A |
| | MIN OF 3` NFPA-72 2-5.2.1.6 |
| | |
| | 5)NOTE: PLEASE NOTE THE MISSING SMALL |
| | APPLIANCE CIRCUITS ON PANEL SCHEDULES. |
| | 210-11-C-1 |
| | |
| | 6)NOTE: PLEASE NOTE THAT ONLY ONE PANEL |
| | IS SHOWN ON PLANS? RISER SHOWS TWO? |
| | |
| | 7)PLEASE NOTE THAT THE ELECTRICAL PANEL |
| | IS SHOWN IN BATHROOM. THIS IS NOT |
| | PERMITTED PER 240-24E. PLEASE NOTE THAT |
| | PANEL CLEARENCE PER 110-26 |
| | |
| | 8)NOTE:PLEASE NOTE THAT PANEL SCHEDULES |
| | DO NOT CORRELATE>>> "A" SHOWS 3-AHU`S |
| | AND "B" SHOWS CU`S 1,2A,2B AND 3??? |
| | PLEASE CLARIFY. |
| | |
| | 9)NOTE: PLEASE SHOW ALL AHU`S AND CU`S |
| | ON PLANS AND DISCONNECTS PER 440-11 AND |
| | RECEPTS FOR SERVICE. |
| | |
| | 10)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS BETWEEN MAIN AND |
| | PANEL "A". 250-122 |
| | |
| | 11)NOTE: PLEASE CLARIFY WHERE PANEL "B" |
| | IS BEING FED FROM? PANEL SCHEDULE "A" |
| | DOES NOT HAVE PANEL "B" ON SCHED. |
| | |
| | 12)NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | GREAT ROOM. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |