| Date |
Text |
| 2001-10-23 00:00:00 | ******************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE THAT NO DIAGRAM |
| | WAS SUBMITTED FOR NEW SERVICE?? 215-5 |
| | SIZES.WIRE,CONDUITS,GROUNDING ETC. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6)NOTE: PLEASE SUBMIT PLANS THAT ARE |
| | MORE CLEAR. PER 104.2.1 AND 104.2.7 |
| | CLARITY OF PLANS |
| | |
| | 7)NOTE: PLEASE NOTE THAT IF THERE IS |
| | GOING TO BE ANY LV TV,OR PHONE, PLEASE |
| | SHOW ON PLANS. OTHERWISE SEPARTE PLANS |
| | WILL HAVE TO BE SUBMITTED AT A LATER |
| | DATE. |
| | |
| | 8))PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE NOTE MISSING LIGHTING IN SOME |
| | LOCATIONS, SHOWN AS "JB" KITCHEN/PORCH/ |
| | LAUNDRY RM/ BATH? ETC/ |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |