| Plan Review Notes For Permit 01101215 |
| Permit Number |
01101215 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-26 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.MANUFACTURER SUBMITTAL DATA/PRODUCT | | | APPROVAL/INSTALLATION FOR THE 3M | | | FIREMASTER WRAP. | | | | | | 2.PLANS INDICATE EF-1 AGAINST EXTERIOR | | | WALL.SHOW COMPLIANCE WITH 1997 SMC | | | 506.1 AND NFPA 96 4-8.2.1.EXHAUST | | | TERMINATION SHALL BE A MINIMUM OF | | | 10' CLEARANCE FROM THE OUTLET TO | | | ADJACENT BUILDINGS, PROPERTY LINES, | | | AND AIR INTAKES. | | | | | | ADDITIONAL PERMIT REQUIRED FOR FIRE | | | SUPRESSION.PLEASE SUBMIT PLANS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|